66• Fieldbus Controller 750-837, /02x-000, 750-838, /02x-000 Process Image

750-634

The above Incremental Encor Interface module has 5 bytes of input data (6 bytes in cycle duration measurement mode) and 3 bytes of output data. The following tables illustrate the Input and Output Process Image, which has 6 bytes mapped into each image.

Input Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

S

 

 

Status byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

D0

 

 

Counter word

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

2

 

 

D1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

D2*)

 

 

(Periodic time)

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

D3

 

 

Latch word

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

D4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*) If cycle duration measurement mode is enabled in the control byte, the cycle duration is given as a 24-bit value that is stored in D2 together with D3/D4.

These modules present themselves with 1x6 bytes, so that the object 0x3200 for 6 byte Special Modules, Inputs is used. Therefore for each module one Subindex is occupied

Output Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

C

 

 

Control byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

D0

 

 

Counter Setting word

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

2

 

 

D1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

not used

 

 

 

 

4

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These modules present themselves with 1x6 bytes, so that the object 0x3300 for 6 byte Special Modules, Outputs is used. Therefore for each module one Subindex is occupied

WAGO-I/O-SYSTEM 750

CANopen

Fieldbus Controller 750-837, /02x-000, 750-838, /02x-000

• 67

Process Image

 

 

 

750-637

The above Incremental Encor Interface Module has a total of 6 bytes of user data in both the Input and Output Process Image (4 bytes of encor data and 2 bytes of control/status). The following table illustrates the Input and Output Process Image, which have 6 bytes mapped into each image.

Input and Output Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

C0/S0

 

 

Control/Status byte of Channel 1

 

 

n

 

 

 

 

 

 

 

 

 

 

 

1

 

 

D0

 

 

Data Value of Channel 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

D1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

C1/S1

 

 

Control/Status byte of Channel 2

 

 

n+1

 

 

 

 

 

 

 

 

 

 

 

4

 

 

D2

 

 

Data Value of Channel 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

D3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These modules present themselves with 2x3 bytes, so that the object 0x2600 for 3 byte Special Modules, Inputs and the object 0x2700 for 3 byte Special Modules, Outputs are used. Therefore for each module one Subindex is occupied

750-635

The above Digital Pulse Interface module has a total of 4 bytes of user data in both the Input and Output Process Image (3 bytes of module data and 1 byte of control/status). The following table illustrates the Input and Output Process Image, which have 4 bytes mapped into each image.

Input and Output Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

C0/S0

 

 

Control/Status byte

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

1

 

 

D0

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Value

 

 

 

2

 

 

D1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

D2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These modules present themselves with 1x4 bytes, so that the object 0x2800 for 4 byte Special Modules, Inputs and the object 0x2900 for 4 byte Special Modules, Outputs are used. Therefore for each module one Subindex is occupied

WAGO-I/O-SYSTEM 750

CANopen

68• Fieldbus Controller 750-837, /02x-000, 750-838, /02x-000 Process Image

DALI/DSI Master Module

750-641

The DALI/DSI Master module has a total of 6 bytes of user data in both the Input and Output Process Image (5 bytes of module data and 1 byte of control/status). The following tables illustrate the Input and Output Process Image, which have 6 bytes mapped into each image.

Input Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

S

 

 

Status byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

D0

 

 

DALI response

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

2

 

 

D1

 

 

DALI address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

D2

 

 

Message 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

D3

 

 

Message 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

D4

 

 

Message 1

 

 

 

 

 

 

 

 

 

 

 

 

 

These modules present themselves with 1x6 bytes, so that the object 0x3200 for 6 byte Special Modules, Inputs is used. Therefore for each module one Subindex is occupied.

Output Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

C

 

 

Control byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

D0

 

 

DALI command, DSI dimming value

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

2

 

 

D1

 

 

DALI address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

D2

 

 

Parameter 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

D3

 

 

Parameter 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

D4

 

 

Command extension

 

 

 

 

 

 

 

 

 

 

 

 

 

These modules present themselves with 1x6 bytes, so that the object 0x3300 for 6 byte Special Modules, Outputs is used. Therefore for each module one Subindex is occupied.

WAGO-I/O-SYSTEM 750

CANopen

Fieldbus Controller 750-837, /02x-000, 750-838, /02x-000

• 69

Process Image

 

 

 

EnOcean Radio Receiver

750-642

The EnOcean radio receiver has a total of 4 bytes of user data in both the Input and Output Process Image (3 bytes of module data and 1 byte of control/status). The following tables illustrate the Input and Output Process Image, which have 4 bytes mapped into each image.

Input Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

0

 

 

S

 

 

Status byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

D0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data bytes

 

 

n+1

 

2

 

 

D1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

D2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

0

 

 

C

 

 

Control byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

not used

 

 

n+1

 

2

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These modules present themselves with 2x2 bytes, so that the object 0x6401 (also 0x2400 possible) for 2 byte Special Modules, Inputs and the object 0x6411 (also 0x2500 possible) for 2 byte Special Modules, Outputs are used. Therefore for each module two Subindices are occupied.

WAGO-I/O-SYSTEM 750

CANopen

70• Fieldbus Controller 750-837, /02x-000, 750-838, /02x-000 Process Image

MP Bus Master Module

750-643

The MP Bus Master Module has a total of 8 bytes of user data in both the Input and Output Process Image (6 bytes of module data and 2 bytes of control/status). The following table illustrates the Input and Output Process Image, which have 8 bytes mapped into each image.

Input and Output Process Image

 

Sub-

 

 

Offset

 

 

byte Destination

 

 

Remark

 

 

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

C0/S0

 

 

Control /Status byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

C1/S1

 

 

extended Control /Status byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

D0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

3

 

 

D1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

D2

 

 

Data bytes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

D3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

D4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

D5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These modules present themselves with 1x8 bytes, so that the object 0x3600 for 8 byte Special Modules, Inputs and the object 0x3700 for 8 byte Special Modules, Outputs are used. Therefore for each module one Subindex is occupied.